6ES7332-5TB00-0AB0 SIMATIC DP, HART ANALOG OUTPUT en Shenzhen, Guangdong, China

Especificaciones

Condición
nuevo
SIMATIC DP, HART ANALOG OUTPUT SM 332, 2AO, 0/4 - 20MA HART, FOR ET200M WITH IM153-2, 20 PIN
Rated value (dc)
24 V
Reverse polarity protection
Yes
From backplane bus 5 v dc, max.
100 mA
From supply voltage l , max.
150 mA
Power loss, typ.
3.5 W
Number of analog outputs
2
Voltage output, short-circuit protection
Yes
Current output, no-load voltage, max.
19 V
Cycle time (all channels) max.
5 ms
0 to 20 ma
Yes
4 to 20 ma
Yes
For current output two-wire connection
Yes
With current outputs, max.
650 Ω
With current outputs, inductive load, max.
7.5 mH
Voltages at the outputs towards mana
max. 17 V / -0.5 V
Current, max.
60 mA / -1 A
Cable length, shielded, max.
400 m
Resolution with overrange (bit including sign), max.
12 bit; Output value; 8 bit ( sign) read back value
Conversion time (per channel)
40 ms
For resistive load
2.5 ms
For capacitive load
4 ms
For inductive load
2.5 ms
Output ripple (based on output area, bandwidth 0 to 50 khz), ( /-)
0.02 %
Linearity error (relative to output range), ( /-)
0.03 %
Temperature error (relative to output range), ( /-)
0.01 %/K
Crosstalk between the outputs, min.
130 dB
Repeat accuracy in steady state at 25 °c (relative to output area), ( /-)
0.0050 %
Current, relative to output area, ( /-)
0.15 %
Substitute values connectable
Yes; Parameterizable
Diagnostic alarm
Yes; Parameterizable
Diagnostic functions
Yes; Parameterizable
Diagnostic information readable
Yes
Diagnostics
Yes
Overrange
Yes
Wire break
Yes; as of output value > 0.5 mA
Wire break in actuator cable
Yes
Hart communication active
Yes; green LED (H)
Group error sf (red)
Yes; Additional group message per channel
Channel error indicator f (red)
Yes; per channel
Module for ex(i) protection
Yes
Co (permissible external capacity), max.
230 nF
Io (short-circuit current), max.
66 mA
Lo (permissible external inductivity), max.
7.5 mH
Po (power of load), max.
506 mW
Uo (output no-load voltage), max.
19 V
Um (fault voltage), max.
60 V; DC
Ta (permissible ambient temperature), max.
60 °C
Between the channels and backplane bus
Yes
Galvanic isolation analog outputs
Yes
Between the channels
Yes
Between the channels and the load voltage l
Yes
Between the outputs (ucm)
60V DC/30V AC
Between m internally and the outputs
60V DC/30V AC
Channels against backplane bus and load voltage l
1500 V AC
Channels among one another
1500 V AC
Load voltage l against backplane bus
500 V DC
Fm approval
Available soon
Type of protection acc. to en 50020 (cenelec)
[EEx ib] IIC
Type of protection acc. to fm
Class I, Division 2, Group A, B, C, D T4; Class I, Zone 2, Group IIC T4
Test number kema
97 ATEX 2359 X
Type of protection acc. to kema
II3 (2) G Eex nA [ib] IIC T4
Width
40 mm
Height
125 mm
Depth
120 mm
Weight, approx.
280 g
Subcategoría
Plc
Subcategoría 2
S7-300
Subcategoría 3
Siemens plc all
ID de Anuncio
88365427

Descripción

SIEMENS S7-300 6ES73325TB000AB0 SIMATIC DP, HART ANALOG OUTPUT,SM 332, 2AO, 0/4 - 20MA HART,,FOR ET200M WITH IM153-2, 20 PINSIMATIC DP, HART ANALOGAUSGABE,,SM 332, 2AA, 0/4 - 20MA HART,,FUER ET200M MIT ANSCHALTUNG,IM 153-2, 20-POLIGSIMATIC DP, SORTIE ANAL

Contactar al vendedor

Fabricante
N/A
Modelo
6ES7332-5TB00-0AB0
Ubicación
🇨🇳 Shenzhen, Guangdong, China

¿Le interesa esta máquina?

Capacidad de respuesta del vendedor:

4.5