6ES7635-2EC02-0AE3 C7-635 KEYS, 24 DI, 16 DO, 5 AI, 2 AO en Shenzhen, Guangdong, China

Especificaciones

Condición
nuevo
Artikelnummer
6ES7635-2EC02-0AE3
24 v dc
Yes
Permissible range, lower limit (dc)
20.4 V
Permissible range, upper limit (dc)
28.8 V
Rated value (dc)
24 V
From load voltage l (without load), max.
70 mA
From load voltage l , max.
100 mA
Power loss, typ.
14 W
Integrated
1
Expandable
No
Plug-in (mmc)
Yes
Plug-in (mmc), max.
8 Mbyte
Present
Yes
Without battery
Yes; Program and data
For bit operations, typ.
0.1 µs
For bit operations, max.
0.2 µs
For word operations, typ.
0.2 µs
For fixed point arithmetic, typ.
2 µs
For floating point arithmetic, typ.
3 µs
Number, max.
511
Size, max.
16 kbyte
Number of free cycle obs
1; OB 1
Number of time alarm obs
1; OB 10
Number of delay alarm obs
1; OB 20
Number of time interrupt obs
1; OB 35
Number of process alarm obs
1; OB 40
Number of startup obs
1; OB 100
Number of asynchronous error obs
5; OB 80, 82, 85, 86, 87
Per priority class
8
Additional within an error ob
4
Number
1
Adjustable
Yes
Lower limit
48 Ω
Upper limit
4 kΩ
Preset
No retentivity
Retentivity available
Yes; MB 0 to MB 255
Retentivity preset
MB 0 to MB 15
Number of clock memories
8; 1 memory byte
Per priority class, max.
510 byte
Inputs
244 byte
Outputs
244 byte
Inputs, of which central
253
Outputs, of which central
250
Via cp
4
Fm
8
Cp, point-to-point
8
Cp, lan
10
Racks, max.
4
Modules per rack, max.
8; In rack 3 max. 7
Hardware clock (real-time clock)
Yes
Battery-backed and synchronizable
Yes
Deviation per day, max.
10 s
Backup time
6 wk; At 40 °C ambient temperature
Number/number range
0
Range of values
0 to 2^31 hours (when using SFC 101)
Granularity
1 hour
Retentive
Yes; Must be restarted at each restart
Supported
Yes; via CP and loadable FC
To mpi, master
Yes
To mpi, slave
Yes
In as, master
Yes
Number of digital inputs
24
Of which inputs usable for technological functions
16
Integrated channels (di)
24
Input characteristic curve in accordance with iec 61131, type 1
Yes
Up to 40 °c, max.
2 A
Up to 60 °c, max.
12
Rated value, dc
24 V
For signal "0"
-3 to 5 V
For signal "1"
15 to 30 V
For signal "1", typ.
9 mA
Parameterizable
Yes; by software
Rated value
3 ms
At "0" to "1", max.
8 µs
Cable length, shielded, max.
200 m
Cable length unshielded, max.
600 m
Shielded, max.
1 000 m
Unshielded, max.
600 m
Number of digital outputs
16
Of which high-speed outputs
4
Integrated channels (do)
16
Short-circuit protection
Yes; Clocked electronically
Response threshold, typ.
1 A
Limitation of inductive shutdown voltage to
L (-48 V)
Controlling a digital input
Yes
Lamp load, max.
5 W
For signal "1", min.
L (-0.8 V)
For signal "1" rated value
500 mA
For signal "1" permissible range, min.
5 mA
For signal "1" permissible range, max.
0.6 A
For signal "1" minimum load current
5 mA
For signal "0" residual current, max.
0.5 mA
For uprating
No
For redundant control of a load
Yes
With resistive load, max.
100 Hz
With inductive load, max.
0.5 Hz
On lamp load, max.
100 Hz
Of the pulse outputs, with resistive load, max.
2.5 kHz
Integrated channels (ai)
4 1
Number of analog inputs for voltage/current measurement
4
Number of analog inputs for resistance/resistance thermometer measurement
1
Permissible input voltage for current input (destruction limit), max.
2.5 V; Permanent
Permissible input voltage for voltage input (destruction limit), max.
30 V; Permanent
Permissible input current for voltage input (destruction limit), max.
0.5 mA; Permanent
Permissible input current for current input (destruction limit), max.
50 mA; Permanent
Technical unit for temperature measurement adjustable
Yes; Degrees Celsius / degrees Fahrenheit / Kelvin
Current
Yes
Resistance thermometer
Yes
Resistance
Yes
0 to 10 v
Yes
Input resistance (0 to 10 v)
100 kΩ
10 v to 10 v
Yes
Input resistance (-10 v to 10 v)
100 kΩ
0 to 20 ma
Yes
Input resistance (0 to 20 ma)
50 Ω
20 to 20 ma
Yes
Input resistance (-20 to 20 ma)
50 Ω
4 to 20 ma
Yes
Input resistance (4 to 20 ma)
50 Ω
Pt 100
Yes
Input resistance (pt 100)
10 MΩ
No-load voltage, typ.
2.5 V
Measuring current, typ.
1.8 to 3.3 mA
0 to 600 ohm
Yes
Input resistance (0 to 600 ohm)
10 MΩ
For resistance thermometer
Pt 100
Number of analog outputs
2
Integrated channels (ao)
2
Voltage output, short-circuit protection
Yes
Voltage output, short-circuit current, max.
55 mA
Current output, no-load voltage, max.
17 V
10 to 10 v
Yes
For voltage output two-wire connection
Yes; Without compensation of the line resistances
For voltage output four-wire connection
No
For current output two-wire connection
Yes
With voltage outputs, min.
1 kΩ
With voltage outputs, capacitive load, max.
0.1 µF
With current outputs, max.
300 Ω
With current outputs, inductive load, max.
0.1 mH
Voltages at the outputs towards mana
16 V; Permanent
Current, max.
50 mA; Permanent
Measurement principle
Actual value encryption (successive approximation)
Resolution with overrange (bit including sign), max.
12 bit
Integration time, parameterizable
Yes; 2,5 / 16,6 / 20 ms
Permissible input frequency, max.
400 Hz
Conversion time (per channel)
1 ms
Time constant of the input filter
0.38 ms
Basic execution time of the module (all channels released)
1 ms
For resistive load
0.6 ms
For capacitive load
1 ms
For inductive load
0.5 ms
For voltage measurement
Yes
For current measurement as 2-wire transducer
Yes; with external supply
For current measurement as 4-wire transducer
Yes
For resistance measurement with two-wire connection
Yes; Without compensation of the line resistances
For resistance measurement with three-wire connection
No
For resistance measurement with four-wire connection
No
2-wire sensor
Yes
Permissible quiescent current (2-wire sensor), max.
1.5 mA
Temperature error (relative to input range), ( /-)
0.006 %/K
Crosstalk between the inputs, min.
60 dB
Repeat accuracy in steady state at 25 °c (relative to input area), ( /-)
0.06 %
Output ripple (based on output area, bandwidth 0 to 50 khz), ( /-)
0.1 %
Linearity error (relative to output range), ( /-)
0.15 %
Temperature error (relative to output range), ( /-)
0.01 %/K
Crosstalk between the outputs, min.
60 dB
Repeat accuracy in steady state at 25 °c (relative to output area), ( /-)
0.06 %
Voltage, relative to input area, ( /-)
0.7 %; Linearity error /- 0.06 %
Current, relative to input area, ( /-)
0.7 %; Linearity error /- 0.06 %
Resistance, relative to input area, ( /-)
3 %; Linearity error /- 0.2%
Voltage, relative to output area, ( /-)
0.7 %
Current, relative to output area, ( /-)
0.7 %
Resistance thermometer, relative to input area, ( /-)
3 %
Series mode interference (peak value of interference < rated value of input range), min.
30 dB
Common mode interference, min.
40 dB
Mpi
No
Cable length, max.
50 m; without repeater
Interface type
Integrated RS 485 interface
Physics
RS 485
Isolated
Yes
Power supply to interface (15 to 30 v dc), max.
200 mA
Point-to-point connection
No
Transmission rate, max.
12 kbit/s
Pg/op communication
Yes
Routing
Yes
S7 communication, as client
No
S7 communication, as server
Yes
Number of connection resources
12
Number of connections, max.
12; For PG/OP communication
Number of connections (of which reserved), max.
1 for PG, 1 for OP
Number of dp slaves, max.
32
Equidistance mode support
Yes
Sync/freeze
Yes
Activation/deactivation of dp slaves
Yes
Direct data exchange (slave-to-slave communication)
Yes
Dpv1
No
Inputs, max.
244 byte
Outputs, max.
244 byte
Gsd file
The latest GSD file is available at:
Address area, max.
32
User data per address area, max.
32 byte
Number of gd loops, max.
4
Number of gd packets, max.
4
Number of gd packets, transmitter, max.
4
Number of gd packets, receiver, max.
4
Size of gd packets, max.
22 byte
Size of gd packet (of which consistent), max.
22 byte
User data per job, max.
180 kbyte; With PUT/GET
User data per job (of which consistent), max.
64 byte
As server
Yes
As client
Yes; Via CP and loadable FB
Overall
12
Usable for pg communication
11
Reserved for pg communication
1
Adjustable for pg communication, min.
1
Adjustable for pg communication, max.
11
Usable for op communication
11
Reserved for op communication
1
Adjustable for op communication, min.
1
Adjustable for op communication, max.
11
Usable for s7 basic communication
8
Reserved for s7 basic communication
8
Adjustable for s7 basic communication, min.
0
Adjustable for s7 basic communication, max.
8
Usable for routing
4; max.
Number of login stations for message functions, max.
12; Depending on the configured connections for PG/OP and S7 basic communication
Process diagnostic messages
Yes
Simultaneously active alarm-s blocks, max.
40
Status block
Yes
Single step
Yes
Number of breakpoints
2
Status/control variable
Yes
Variables
Inputs, outputs, memory bits, DB, times, counters
Number of variables, max.
30
Of which status variables, max.
30
Of which control variables, max.
14
Forcing
Yes
Number of entries, max.
100
Number of counters
4; See "Technological Functions" manual
Counting frequency (counter) max.
60 kHz
Frequency measurement
Yes
Number of frequency meters
4; up to 60 kHz (see "Technological Functions" manual)
Controlled positioning
Yes
Integrated function blocks (closed-loop control)
PID controller (see "Technological Functions" manual)
Pid controller
Yes
Number of pulse outputs
4; Pulse width modulation up to 2.5 kHz (see "Technological Functions" Manual)
Limit frequency (pulse)
2.5 kHz
Galvanic isolation digital inputs
Yes
Between the channels
No
Between the channels and the backplane bus
Yes
Galvanic isolation digital outputs
Yes
Between the channels, in groups of
8
Galvanic isolation analog inputs
Yes; common for analog I/O
Galvanic isolation analog outputs
Yes; common for analog I/O
Between different circuits
75 VDC / 60 VAC
Between inputs and mana (ucm)
8 V DC
Between mana and m internally (uiso)
75 VDC / 60 VAC
Isolation tested with
500 V DC
Step 7
Yes; V5.2 SP1 with HW update
Command set
see instruction list
Nesting levels
8
System functions (sfc)
see instruction list
System function blocks (sfb)
see instruction list
Lad
Yes
Fbd
Yes
Stl
Yes
Scl
Yes
Cfc
Yes
Graph
Yes
Higraph®
Yes
User program protection/password protection
Yes
Width
260 mm
Height
273.8 mm
Depth
80 mm
Mounting cutout, width
231 mm
Mounting cutout, height
257 mm
Weight, approx.
1 500 g
Last modified:
31.07.2014
Subcategoría
Plc
Subcategoría 2
Siemens plc all
Subcategoría 3
C7/rack pc,box pc
ID de Anuncio
88363499

Descripción

SIEMENS C7/RACK PC,BOX PC 6ES76352EC020AE3 SIMATIC C7-635 KEYS,,COMPACT UNIT,WITH INTEGRATED COMPONENTS:,S7-300 CPU314C-2 DP AND OP170B,,24 DI, 16 DO, 5 AI, 2 AO;,MICRO MEMORY CARD AND,CONNECTOR SET REQUIREDSIMATIC C7-635 TASTEN,,KOMPLETTGERAET,MIT INTEGR

Contactar al vendedor

Fabricante
N/A
Modelo
6ES7635-2EC02-0AE3
Ubicación
🇨🇳 Shenzhen, Guangdong, China

¿Le interesa esta máquina?

Este vendedor fue contactado 1 vez durante la semana anterior.

Capacidad de respuesta del vendedor:

4.5