GF302D1S portable three phase electricity meter test system with reference meter and current & voltage source en Pekín, China
Nuevo
Doubleclick to zoom in
Contacte al vendedor
para más fotos y información.
Especificaciones
- Condición
- nuevo
- Accuracy
- 0.002Hz
- Power supply
- One phase AC 85-265V, frequency 50/60Hz.
- Range
- 40Hz-70Hz
- Resolution
- 0.001Hz
- Error
- 0.0005
- Harmonious
- 2nd-63rd
- Range (direct connection)
- 1mA-120A
- Error (direct connection)
- ±0.02% (10mA-120A)±0.05% (1mA-10mA)
- Clamp on cts (optional)
- 5A,20A, 100A, 200A, 500A, 1000A, 2000A, 3000A
- Active power (direct connection)
- ±0.02% (0.01A-120A)±0.05% (0.001A-0.01A)
- Reactive power (direct connection)
- ±0.05% (0.1A-120A)
- Active power (clamp on cts)
- ±0.2% (0.001A-120A)
- Reactive power (clamp on cts)
- ±0.5% (0.001A-120A)
- Active energy (direct connection)
- ±0.02% (0.01A-120A)±0.05% (0.001A-0.01A)
- Reactive energy (direct connection)
- ±0.05% (0.01A-120A)
- Active energy (clamp on cts)
- ±0.2% (0.001A-120A)
- Reactive energy (clamp on cts)
- ±0.5% (0.001A-120A)
- Range (u1, u2, u3)
- 0-500V
- Adjustment range
- -1~0~1
- Adjustment fineness
- 0.01% RG, 0.1% RG, 1% RG, 10% RG as optional.
- Stability
- <0.01% /120s
- Distortion
- ≤0.3% (non-capacitive load)
- Output load
- Each phase 25VA or 50VA
- Range (i1, i2, i3)
- 0-120A
- Max output load
- 50VA or 100VA;
- Active power output stability
- <0.01% RG/120s
- Reactive power output stability
- <0.02% RG/120s
- Active power output accuracy
- 0.05%RG
- Reactive power output accuracy
- 0.1%RG
- Output adjustment range
- 0°-359.999°
- Output adjustment fineness
- 10, 1, 0.1, 0.01 as optional.
- Measurement accuracy
- 0.0005
- Harmonic number
- 2-63times
- Harmonic content
- 0-40%
- Harmonic phase
- 0-359.99
- Harmonic setting accuracy
- (10% ±0.1% )RD(2)
- Energy pulse type
- Support active and reactive pulse, the highest frequency power pulse input is 2MHz.
- Active energy pulse output
- 5V, 10mA
- Color lcd
- 7"STN (800×480), touch
- Communication port
- RS232, USB2.0
- Vector diagram
- Yes
- Waveform
- Yes
- Energy register test
- Yes
- Ct ratio test
- Yes
- Ct pt burden test
- Yes
- Local parameter input
- Yes
- Wiring emulation
- Yes
- Self-calibration
- Yes
- Recorder check
- Yes
- Data storage
- Yes
- Gps
- Yes, optional
- Data storage qty
- 10000
- External extend memory
- Yes
- Communicate with pc
- Yes
- Upload data
- Yes
- Keyboard
- Yes
- Standard
- iec 62053-21,22,23; iec 60736; ansi c12.20-2002; jjg 597-2005; jjg596-2012; jjg 1085-2013; jjf 68-2019; dl/t 826-2002; dl/t 1478-2015; dl/t 448-2016 ; EN 50470
- Isolation protection
- IEC 61010-12001
- Measurement category
- 300V CAT III, 600V CAT II
- Degree of protection
- IP42
- Declaration of conformity
- CE & CNAS certified
- Dimensions (w×d×h)(mm)
- 570 x 416 x 282
- Weight (kg)
- 25
- Ambient temperature
- -25°C to +50°C
- Storage temperature
- -30°C to +65°C
- Relative humidity
- 15% -95%
- Subcategoría
- Machinery
- Subcategoría 2
- Energy meter calibration
- ID de Anuncio
- 84813385
Descripción
The GF302D1S portable three phase electricity meter test system consists of an integrated 0.05% three-phase current and voltage source and a three-phase electronic reference meter of accuracy class 0.02.